LNG Peak-Shaving & Marine Export Facility Safety Schematic
49 CFR § 193.2057(a): Each LNG container and LNG transfer system must have a thermal exclusion zone computed in accordance with Section 2.2.3.2 of NFPA 59A (2001) with a wind speed producing the maximum exclusion distance.
Side-by-Side Edition Redline Diff (`NFPA 59A 2001 vs. 2019 Edition` & IBR Set)
NFPA 59A (2001) § 2.2.3.2: Thermal radiation distances shall be calculated using deterministic incident flux limits of 1,600 Btu/ft²-hr (5 kW/m²) at the property line that can be built upon, and 3,000 Btu/ft²-hr (9 kW/m²) for offsite congregation areas.
NFPA 59A (2019) § 5.3.2 & Chapter 19: Retains deterministic 1,600 Btu/ft²-hr (5 kW/m²) property-line threshold while adding validated solid-flame / PHAST radiative atmospheric transmissivity models and Chapter 19 Quantitative Risk Assessment (QRA) individual risk contours (10⁻⁵ / yr).
Inspectors auditing Marine Export and Peak-Shaving facilities must verify whether a Special Permit or Letter of Design Approval authorizes 2019 QRA contours over the baseline 2001 deterministic table.